What is the diameter of 4 3 MC cable?

What is the diameter of 4 3 MC cable?

0.941
Under raised floors for technology equipment conductors and cables. Installation in cable tray and approved raceways. Class I Div. 2, Class II Div….Product Details.

Cable Type MC
Wire Size 4 AWG
# of Conductors 3 Conductors w/ Ground
O.D. (Inches) 0.941
Ampacity 95

What is the diameter of 8 2 MC cable?

0.69
PVC/Nylon type THHN insulation in accordance to UL 83, flame resistant, meeting UL VW-1….Product Details.

Cable Type MC
# of Conductors 2 Conductors w/ Ground
O.D. (Inches) 0.69
Ampacity 55

What is the difference between armored cable and MC cable?

Armored cable (AC) first appears in the 1903 NEC. The biggest difference between the two cable systems is that MC has full size ground wire while AC uses a combination of the jacket and a thin bonding strip or wire to function as the equipment ground.

What is armor clad cable?

A Metal Clad Cable, also referred to as MC Cable, is a corrosion-resistant metal cable containing insulated copper or aluminum connectors.

What is the diameter of 6 3 MC cable?

0.590″ to 0.920″
Snap-In MC Connector for Aluminum and Steel MC, Material: Die-Cast Zinc, Cable Diameter 0.590″ to 0.920″, For the Following MC Sizes: 10/3, 10/4, 8/2, 8/3, 8/4, 6/2, 6/3.

What is the diameter of 12 2 MC cable?

0.477
12 gauge 2 conductors w/ ground copper MC Cable. Sold by the spool….Ampere Rating THHN: 20.

Cable Type MC
# of Conductors 2 Conductors w/ Ground
Conductor Material Bare Copper
Stranded or Solid Solid
O.D. (Inches) 0.477

What is the diameter of 14 2 MC cable?

0.441
14 gauge 2 conductors w/ ground copper MC Cable. Sold by the spool….Ampere Rating THHN: 15.

Cable Type MC
# of Conductors 2 Conductors w/ Ground
Conductor Material Bare Copper
Stranded or Solid Solid
O.D. (Inches) 0.441

Is MC cable suitable for outdoor use?

These cables can be installed either indoors or outdoors and in exposed and concealed locations. They can be direct buried, where identified for such use. Type MC cable with a nonmetallic jacket can also be used in a wet location.

Can you run MC cable exposed?

Section 330.15 states: Exposed runs of cable, except as provided in 300.11(A), shall closely follow the surface of the building finish or running boards. Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be subject to physical damage.

Can you use MC cable outside?

The interlocking metal tape armor Type MC cable is required to have a bare or insulated equipment grounding conductor in addition to any other conductors within the cable. These cables can be installed either indoors or outdoors and in exposed and concealed locations.

Can you use Armoured cable outside?

Armoured cables and cables having an earthed metal sheath suitable for use as a protective conductor may be buried directly in the ground without further protection, except against corrosion, which may be negated by the provision of a plastic covering. Surface fixed cables may be fixed to permanent structures.

What sizes does MC cable come in?

MC Cable is available in in stranded or solid copper for sizes #14 AWG to #10 AWG and compact strand for sizes #8 AWG to #4/0 AWG. An optional outer PVC jacket is also available upon request.

How do you cut armored cables without damaging them?

The best method is to use an armored cable rotary cutter. This tool uses a small cutting wheel powered by a hand crank and will cut only through the armor, leaving the wires undamaged every time. Apply firm pressure to the handle, but don’t squeeze too hard or the crank will be difficult to turn. 7 / 12

What is metal clad cable used for?

Metal Clad Cable may be used for branch, feeder and service for distribution in commercial, industrial, and multi-residential construction. They are suitable for installation in motion picture studios, theaters, and places of assembly (100 people or more) per NEC Articles 230.43, 300.22 (C), 330, 396, 518, 520, 530 and 645.

How much exposed wire should be in a cable box?

There should be a minimum of 6-8-in. of exposed wire inside the box. Plastic anti-short bushings protect the wires from being damaged by the sharp edge of the armor when the cable gets clamped down into a connector.

author

Back to Top