Where is hospital grade MC required?

Where is hospital grade MC required?

Branch circuits in areas of patient care in hospitals, nursing homes, outpatient facilities, dental offices, clinics and medical centers (other than emergency, life safety or critical care locations), Places of Assembly, under raised floors, above suspended ceilings, environmental air-handling spaces, exposed or …

What makes an outlet hospital grade?

In addition to complying with the general use receptacle Listing requirements, hospital grade receptacles incorporate additional construction features and are subjected to additional performance requirements. These include grounding reliability, assembly integrity, strength and durability tests.

Which of the following is a requirement for receptacles located at patient bed sites?

14 receptacles
A minimum of 14 receptacles must now be installed in patient bed locations in critical-care areas, and they must be listed and identified as “hospital grade.” The branch-circuit equipment grounding conductor connected to the grounding terminal of these receptacles is also required to be insulated copper.

Where are tamper resistant receptacles required in hospitals?

NFPA 70-2011, Article 517.18(C), requires tamper-resistant receptacles in pediatric locations of health care facilities (e.g., hospitals, physician offices and therapy areas), including patient rooms, bathrooms, playrooms, activity rooms and patient care areas of designated pediatric locations.

Do exam rooms need hospital grade receptacles?

The short answer is no. The NEC generally does not require hospital-grade receptacles for exam rooms in medical buildings. The NEC requires listed hospital-grade receptacles in patient bed locations of general care areas as indicated in 517.18(B). A minimum of four such receptacles must be provided.

Are hospital grade receptacles tamper resistant?

Hospital-Grade Tamper-Resistant Compact Design Receptacle, Back & Side Wire, 20A, 125V, Ivory | Commercial Receptacles | Outlets and Receptacles | Wiring Devices.

Do hospital grade receptacles have isolated ground?

Isolated ground (IG) receptacles (electrical outlets) are most often found in hospitals and other medical facilities, commercial buildings, and some industrial settings. This special receptacle may have an orange face with a small green triangle or a white face with a small orange triangle.

What is difference between hospital grade outlets and a regular receptacle?

Hospital grade receptacles have the same markings appearing on general use receptacles, but include additional markings denoting their intended use. These additional markings include the phrase “Hospital Grade” or “Hosp.

Are hospital-grade receptacles tamper resistant?

How many receptacles are required in an operating room?

36 receptacles
Section 517.19(C) requires each operating room in a critical care area to be provided with at least 36 receptacles. Of these, at least 12 must be connected to either the normal system branch circuit or a critical branch circuit supplied by a different transfer switch than the other receptacles at the same location.

How often should GFCI receptacles be tested?

GFCIs should be tested monthly to ensure they are in working condition. Whether you have a receptacle or circuit breaker GFCI, pushing the TEST button should turn off the power to the circuit. For the receptacle-type GFCI, pushing the TEST button should cause the RESET button to pop up.

Can I use red outlets in hospital?

The red outlets (sometimes referred to as sockets) in hospitals and medical facilities indicate that they are on emergency backup power. To be considered “hospital grade” or “medical grade”, the backup power solution usually must provide pure sine wave power to operate sensitive medical equipment.

Do we need hospital-grade receptacles?

The NEC generally does not require hospital-grade receptacles for exam rooms in medical buildings. Keep in mind that owner or engineering specifications may be more restrictive than the NEC’s minimum requirements; therefore, hospital-grade receptacles may be a specification or design requirement, which may exceed the minimum NEC rules.

Are tamper proof outlets required?

Tamper-resistant receptacles, or outlets, have been required in most areas of homes in the United States since 2008 per the National Electrical Code (NEC). These outlets, which feature spring-loaded shutters or flaps that snap closed when the outlet isn’t in use, help to prevent shocks that may otherwise occur if a child tries to place a metal object into one of the openings.

Is tamper resistant outlet required?

That’s why tamper resistant outlets are so convenient; they work automatically and require no upkeep from you. Tamper proof outlets are currently required in all hospitals and new homes. If you have a child or are planning to have children in the future, they are a great investment.

What are hospital grade outlets?

Hospital Grade Hospital grade outlets are specially designed for situations where an outlet needs to be highly durable and reliable, as would be the case with outlets used in hospitals and medical facilities.

author

Back to Top