How do you calculate star Delta overload?

How do you calculate star Delta overload?

Overload Relay in Winding: In the windings means that the overload is placed after the point where the wiring to the contactors are split into main and delta. The overload then always measures the current inside the windings. The setting of Overload Relay (In Winding) =0.58 X FLC (line current).

How do you calculate overload setting?

The overloads are determined using 125% of the FLA, 7A x 1.25 = 8.75A. The maximum allowable size for the overloads is 9.8A. The overloads can be sized at 140% of the FLA if the overloads trip at rated load or will not allow the motor to start, 7A x 1.4 = 9.8A.

How is overload relay calculated?

Thermal Overload Relay setting = 100% x Full Load Current (Line).

  1. Thermal Overload Relay setting = 100% x Full Load Current (Line).
  2. Thermal Overload Relay setting = 100%x6 = 6 Amp.

How can I select OLR for star delta starter?

Size of Star Contactor (Starting Condition) = 33%X Full Load Current (Line). Size of Star Contactor =33%x13 = 4 Amp. Size of Main Contactor (Starting-Transition-Running) = 58%X Full Load Current (Line). Size of Main Contactor =58%x13 = 8 Amp.

How is motor current rating calculated?

The motor FLA calculator uses the following formulas:

  1. Single Phase AC Motor FLA (Amperes) = (P [kW] × 1000) / (V × cos ϕ)
  2. Single Phase AC Motor FLA (Amperes) = (P [HP] × 746) / (V × cos ϕ × η)
  3. Three Phase AC Motor FLA (Amperes) = (P [kW] × 1000) / (V × 1.732 × cos ϕ)

How do you calculate the full load current of a motor?

Full load current I, I =P. / 1.732 * V Amps.

How do you calculate overload protection?

The overload protection is sized per the motor nameplate current rating, not the motor full load current (FLC) rating. Thus, 60A×1.25=75A. Overload protection shall not exceed 75A, so you need to use a 70A dual-element fuse [240.6(A) and 430.32(A)(1)].

What is an overload factor?

The purpose of the overload factor, KO, is to account for externally applied loads in excess of the nominal tangential load Wt. A typical example is the variation in torque from an internal combustion engine.

How do you calculate relay settings?

Calculation of Over Current Relay Setting:

  1. Over Load Current (In) = Feeder Load Current X Relay setting = 384 X 125% =480 Amp.
  2. Required Over Load Relay Plug Setting= Over Load Current (In) / CT Primary Current.
  3. Required Over Load Relay Plug Setting = 480 / 600 = 0.8.

Where to place the overload protection on a star delta starter?

For a star-delta starter we have the possibility to place the overload protection in two positions, in the line or in the windings. If Over Load Relay supply the entire motor circuit and are located ahead of where the power splits to the Delta and Star contactors, so O/L Relay size must be based upon the entire motor Full Load Current.

What is a star delta starter used for?

Therefore star-delta starters are widely used for motors rated over 10hp or 7.5kW (even small motors can be started used the star-delta method). This can reduce current inrush to 1/3 of direct-on-line starting current.

What is the difference between a star and a Delta Motor?

In star connection at start, the motor draws and delivers 1/3 of its full rated power. When the starter switches over to Delta, the motor draws full power, but since the contactors and the overload relay are usually wired within the Delta, you need to use contcators and relay which are only rated 1/√3 =58% of the full rated power of the motor.

What is the current rating of deltadelta contactor?

Delta contactor rating = 58%X Full Load Line Current = 7.96A Star contactor rating = 33%X Full Load Line Current = 4.53A The contactor must be selected such that its rating is higher than the calculated values. Read more about making and breaking capacities and utilization categorization.

author

Back to Top