What does it mean when an outlet says no equipment ground?
What does it mean when an outlet says no equipment ground?
If you just replace one non-grounded receptacle with a GFCI then it must be marked “No equipment ground”. This can be found in the NEC Article 406.4(D)(2). It is used as a means to install grounded receptacles on a non-grounded circuit and not have to rewire an entire dwelling.
Is no equipment ground safe?
Let’s talk about the last two options. A GFCI-protected grounding-type receptacle without an equipment-grounding conductor is safer than a grounding-type receptacle with an equipment-grounding conductor, but without GFCI protection.
What article of the NEC would you find info on replacing a non grounding receptacle?
Section 406.4(D)(2) provides options to replace the old two-prong receptacle without adding an equipment grounding conductor.
What do you do if your outlet has no ground wire?
You can wire a three-prong outlet to the GFCI by connecting it to the LOAD terminals. That outlet will get ground fault protection from the GFCI. It must also have a label that says “No Equipment Ground.”
Can GFCI replace ungrounded outlet?
GFCI stands for “Ground Fault Circuit Interrupter”. You’ve no doubt seen these before at bathrooms or kitchens, and you can read more about these on a previous post here. These outlets are considered safe to install on an un-grounded circuit, and replaces those inconvenient 2 prong outlets.
Will GFCI work without ground wire?
Yes. A GFCI will work without a ground, though an external tester will not work. A GFCI should only be installed without a ground if no ground is available and it should be clearly marked “NO EQUIPMENT GROUND”.
Is GFCI better than grounding?
A ground fault occurs when the electrical path changes. Hence, a GFCI breaker does work without a ground wire, and according to the National Electric Code, a GFCI will offer better protection from shocks than grounded receptacles alone. Grounding does not protect against electrocution as GFCI does.
Can you install a GFCI without a ground?
A GFCI without ground wire isn’t ideal, but it’s better than a 2-prong outlet. A GFCI outlet will work without a ground wire and it’s legal. If the outlet shorts out for any reason, it will still trip for safety, even without ground. …
Does GFCI work without ground?
Does GFCI replace ground?
It should be noted that the GFCI outlet or breaker does not actually create a path to ground, nor does it make this a grounded outlet. It simply makes the un-grounded outlet safer.
What is a no equipment ground receptacle?
These receptacles shall be marked “No Equipment Ground.” An equipment grounding conductor shall not be connected from the ground-fault circuit-interrupter- type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle.
What does no equipment ground mean on a GFCI outlet?
Grounding-type receptacles supplied through the ground-fault circuit interrupter shall be marked “GFCI Protected” and “No Equipment Ground.” An equipment grounding conductor shall not be connected between the grounding-type receptacles. 406.4 (D) (2) Non–Grounding-Type Receptacles.
What does the 2017 NEC mean for receptacles?
In the 2017 NEC, the code language has changed to require receptacles “ or their cover plates ” to be marked “no equipment ground”. This should prove to be easier for the electrician since the cover plate provides a much larger surface to stick labels on. Below is a preview of the NEC.
Do I need an equipment grounding conductor when replacing receptacles?
When replacing receptacles in one of the older installations where an equipment grounding conductor is not present in the device box, the NEC gives several options. Section 250.130 (C) provides methods to add an equipment grounding conductor where one did not exist so that the replaced receptacle has a functioning equipment ground.